About Us
  • Company
  • News bulletin
  • Subsidiary

Telephone:

0574-65113511

Mobile:

136 1678 3254

E-mail:

sales@iuxpower.com

News bulletin

Specification requirements for 150V45KW-50KW resistance load equipment

Author:IUXPOWER    Date:2019/01/15    869Browsing

The specification of 150V45KW-50KW resistor load equipment requires that the load equipment meets 150V/500A, and the power is 45kW and 8 gears are controlled and loaded independently.

Specification requirements for 150V45KW-50KW resistance load equipment

1. Basic function

The load equipment meets the requirements of 150V/500A, and the power is 45kW and 8 gears are controlled and loaded independently.

two。. Basic parameters

2.1 Devic.

1) Independent control in 8 gears.

2) Power 45~50KW.

3) Voltage 150V.

4) current 500A.

5) resistive load.

2.2 appearance.

1) the famous brand logo is clear and easy to identify.

2) equipment safety warning signs are eye-catching and easy to see.

2.3 Resistance parameters.

R mode reference:


 

R1

R2

R3

R4

R5

R6

R7

R8

Power

10A

20A

20A

100A

100A

100A

100A

100A

Resistance value

15

7.5

7.5

1.5

1.5

1.5

1.5

1.5

 

3. General function

 

Serial number

Function

Description

 

1

Load display

In the loading state, there must be an indicator light or other indication of a resistance.
Has been loaded.

2

Voltage display

The load needs to have the function of voltage display.

3

Current display

Load displays the current load current

4

Temperature display and control

Displays the load temperature value and the temperature controls the start and stop of the cooling fan.

5

General control function

Load requires total output control

6

Alarm function

Over-temperature acousto-optic alarm

7

Protection

Overtemperature protection function

8

Fan fever

Adopt the upper exhaust fan heat mode or the rear exhaust heat dissipation method.