ALC5000 feedback grid simulator

Download

 

 


ALC5000 series single/three-phase feedback power grid simulator adopts pure digital PWM rectification technology, SPWM high-frequency pulse width modulation method, advanced direct digital frequency synthesizer (DDS) waveform generation technology, with full back-irrigation function, can input AC The source energy is fully fed back to the grid; the input power factor is high, the grid pollution is small, the output waveform quality is high, and the dynamic response speed is fast. It can simulate the voltage disturbance, frequency disturbance and three-phase imbalance of the grid; it is used in new energy industries such as storage Grid-connected performance testing of energy inverters, photovoltaic inverters, charging piles and other products。


 

 

◆ Adopt advanced direct digital frequency synthesizer (DDS) waveform generation technology, with high frequency stability and good continuity。

◆ Provide embedded intelligent PC monitoring system。

◆ The output frequency is 45.000-99.999Hz, with 0.001 Hz/10ms variable, can easily and accurately do under-frequency experiment, anti-islanding experiment; LIST, STEP two major modes, can perform 30 groups of different voltages and frequencies Setting of rate and time, and continuous loop test. The running time can be set to 10ms, which can be used to simulate the power grid test, realize the voltage and frequency gradient, step function, with active PFC, easy to complete It is a low voltage and zero voltage ride through test。

◆ You can do over/under voltage, over/under frequency experiments; set the required change voltage or frequency on the programmable panel. After running, every change in voltage or frequency will trigger a level. Do this experiment It is very accurate and convenient。

◆ High measurement accuracy, suitable for current sine half-wave and similar testing of various waveforms with DC component。

◆ Provide readings of root mean square voltage, root mean square current, active power, frequency, power factor, peak current, etc。

◆ For 100% load removal, the response time is within 2ms, the overload capability is strong, and the instantaneous current can withstand 3 times the rated current。

◆ External zero voltage crossing synchronous trigger signal dry contact, which is convenient for users to test。

◆ It has two parts of DC and AC output, among which the DC voltage is not adjustable, and it is fixed 300V (single-phase input) and 500V (three-phase input) (optional)。





ALC5000 feedback type power grid simulation power supply device

model

ALC5005

ALC5010

ALC5015S

ALC5030S

ALC5060S

ALC5100S

ALC5150S

ALC5200S

ALC5300S

ALC5500S

ALC51000S

ALC52000S

capacity

5KVA

10KVA

15KVA

30KVA

60KVA

100KVA

150KVA

200KVA

300KVA

500KVA

1000KVA

2000KVA

Production method

SPWM (Sine Pulse Width Modulation)

 

 

 

enter

Phase

1φ2W+PE single-phase two-wire + ground wire

3φ4W+PE Three-phase four-wire + ground wire

Voltage

220V±15%

380V±15%

frequency

47Hz ~ 63Hz

PowerFactor

0.85-0.99 (active PFC, up to 0.99 under full load)

Currentharmonics

≤5% (above half load)

Output

Phase

1φ2W+PE single-phase two-wire+PE

3φ4W+PE Three-phase four-wire + ground wire

Voltage

0-320VAC

Phase A: 0-320VAC, Phase B: 0-320VAC, Phase C: 0-320VAC, Phase: Φab: 0-359°, Φac; 0-359

Frequency

45~120Hz (40~500Hz configurable, 10~1000Hz customized) 0.1Step

Rated current

21 A

42 A

21 A

42 A

84 A

140 A

210 A

280 A

420 A

700 A

1400 A

2800 A

Crest factor

3 : 1

Reaction time

2 ms

Energy feedback

Energy feedback to the grid

Display LED

Voltage, current, frequency, power, power factor PF

Powersupplyvoltageregulationrate

0.1%

Hello Elena

1 %

Waveform distortion

2% (pure resistive load)

Frequency stability

0.01%

Voltage resolution

0.1V

Frequency resolution

0 . 001 Hz

Current resolution

0.01A

0.1A

1A



Measurementaccuracy

Voltage

0.5%FS+5dgt

Current

0.5%FS+5dgt

power

0.5%FS+5dgt

frequency

0.01%FS+5dgt

Setting accuracy

Voltage

0.5%FS

frequency

0.1%FS

Number of storage groups

A total of 9 groups, each group can memorize voltage and frequency values, and can be easily recalled

Programmable number of groups

Step LIST: a total of 30 groups, each group can run voltage, frequency value, step time; time setting 10ms, cycle number 99999

Gradual STEP: A total of 30 groups, each group can run starting voltage, ending voltage, linear change time; time setting 10ms, cycle number 99999

Harmonics editor

Can edit any harmonic 1-49 times

Communication Interface

RS232C [IEEE488.2 (GPIB) optional]

Current limit setting

O-Max Current

protect

Over current, over temperature, overload, short circuit

cooling method

Forced cooling by fan

Weight (Kg)

75

90

120

150

200

300

600

900

1200

1800

3000

4500

volume

430×800×700

610×1350×1050 

700×1350×1400

900×1730×1610

900×1730×1610*2

900×1730×1610*3

Operating environment

0 ~40℃ (outdoor -20℃ ~ 50℃ needs to be customized) 20~90%RH